s7414-3dp,增加im153-1dp从站,出错
郑志武
发布于2012-11-14 17:23
52
0
标签:
我们单位有一个s7-414-3dp的cpu下挂了连个im153-1(dp4号和5号)机架,现在想再继续增加一个im153-1(dp,6号)机架。
6号机架中个通道为do32*24v,第二个通道为di32*24v.使用的上位机软件为step7v5.5sp2,当硬件下下去之后,cpu就无法工作。诊断数据如下:
diagnosticbufferofmodulecpu414-3dp
orderno./descriptioncomponentversion
6es7414-3xj04-0ab0hardware2
---firmwarev4.1.0
rack:0
slot:3
serialnumber:svpt8378675
event1of112:eventid16#39c4
distributedi/os:stationfailure
addressoftheaffecteddpslave:stationnumber:5
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:8186
log.baseaddressofthedpmaster:8191
requestedob:rackfailureob(ob86)
obnotfound,ordisabled,orcannotbestartedinthecurrentoperatingmode
externalerror,incomingevent
12:44:18.087pm11/13/2012
(coding:16#39c4fe56c0541fff1ffa0105)
event2of112:eventid16#38c7
distributedi/os:stationoperationalagain,buterror(s)inmoduleparameterassignment
addressoftheaffecteddpslave:stationnumber:5
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:8186
log.baseaddressofthedpmaster:8191
requestedob:rackfailureob(ob86)
obnotfound,ordisabled,orcannotbestartedinthecurrentoperatingmode
externalerror,outgoingevent
12:44:18.086pm11/13/2012
(coding:16#38c7fe56c0541fff1ffa0105)
event3of112:eventid16#5961
parameterassignmenterrorinparametersfordistributeds7modules
outputaddress:544ofthemodulewithparameterassignmenterrors
errortype:slotconfiguredforcpuisnotoccupiedorisoccupiedbyaplaceholder,orastationhasfailedortheswitchedi/osystemhaslostitsredundancy.
datarecordnumber:0
operatingmode:stop(internal)
externalerror,incomingevent
12:44:18.084pm11/13/2012
(coding:16#5961ff04c17b007a82200005)
event4of112:eventid16#5961
parameterassignmenterrorinparametersfordistributeds7modules
outputaddress:528ofthemodulewithparameterassignmenterrors
errortype:slotconfiguredforcpuisnotoccupiedorisoccupiedbyaplaceholder,orastationhasfailedortheswitchedi/osystemhaslostitsredundancy.
datarecordnumber:0
operatingmode:stop(internal)
externalerror,incomingevent
12:44:18.083pm11/13/2012
(coding:16#5961ff04c17b007a82100005)
............
如果再次将5号机架的dp插头拨到on位置,并重新下原来的组态(就是把6号从站的硬件组态删除了),cpu就显示一切正常。
但是就算是组态错误,为何错误是发生在原有的5号从站上面呢?
另外,ob85,0b86,ob121,ob122这些我都是有写入cpu的。
请高手帮助分析下,原因何在,谢谢。
佳答案
1、新增加的6号dp从站,硬件拨码地址是否正确
2、5号从站dp的终端电阻拨为off,新增的6号从站终端电阻拨为on
3、通讯速率和通讯距离的问题
对照下面看下:
9.6kbps到187.5kbps:1000米
500kbaud:400米
1.5mbaud:200米
3mbaud到12mbaud:100米
4、更该通讯方式。
让cpu处于中间位置,dp接头终端电阻拨为off,两端的dp从站设备终端电阻拨为on,试一试!
5、注意硬件组态的型号和版本要和实际事物型号和版本相对应。