s7-300 cpu317f-2 pn/dp的PLC安全程序修改后编译失败
	                        
	                            刘玉蓉
	                            发布于2014-12-10 17:31
	                            
	                                
	                                5
	                            
	                            
	                                
	                                0
	                            
	                            
	                            标签:
	                        
	                     
	                    
	                        s7-300 cpu317f-2 pn/dp的plc安全程序我调试需要,修改后编译失败,Safety program compilation (320:182),Cannot compile due to inconsistencies
between the F-shared DB and the hardware
configuration. Compile the hardware
configuration again with the "CPU contains
safety program" option set.然后编译不成功,下载不了。
												 				佳答案
 提示的意思是你需要重新编译硬件组态,因为安全模块变频器等硬件和你程序中现有的F-DB不能通过一致性检查,你试试重新编译硬件组态,然后再编译安全程序;