技成培训网 技成学习APP 技成工具箱 技成企业服务

欢迎回到技成培训网

技成培训网

电工题库宝典

技成电工课堂

PLC练习题

技成PLC课堂

变频器故障查询

技成PLC学吧

伺服驱动故障查询

技成PLC网校

当前位置:技成首页 > 文章中心 > 技成百科 > 西门子PLC CPU 313C-2DP 频繁报SF故障

西门子PLC CPU 313C-2DP 频繁报SF故障

刘玉蓉 发布于2014-11-14 17:18 2 0 标签:

PLC CPU 为6ES7313C-2DP 。2014年5月14-16日利用CPU的诊断功能,故障信息如下:
1)2014年5月13日I/O access error, reading;P area, double-word access, Access address: 352;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, double-word access, Access address: 356;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。
I/O access error, reading;P area, word access, Access address: 368;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, word access, Access address: 372;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。I/O access error, reading;P area, word access, Access address: 376;Requested OB: I/O access error OB (OB122) ;External error, Incoming event。
I/O access error, writing;P area, word access, Access address: 336;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 338;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 340;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 342;Requested OB: I/O access error OB (OB122);External error, Incoming event。STOP caused by I/O management;Internal error, Incoming event。
2)2014年5月15日I/O access error, reading;P area, word access, Access address: 368;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, reading;P area, word access, Access address: 372;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, reading;P area, word access, Access address: 376;Requested OB: I/O access error OB (OB122);External error, Incoming event。
I/O access error, writing;P area, word access, Access address:336;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 338;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 340;Requested OB: I/O access error OB (OB122);External error, Incoming event。I/O access error, writing;P area, word access, Access address: 342;Requested OB: I/O access error OB (OB122);External error, Incoming event。
3)2014年5月16日I/O access error, reading;P area, double-word access, Access address:352;Requested OB: I/O access error OB (OB122);External error, Incoming event。检查处理如下:
1)对PLC各模块之间的总线连接器进行检查紧固。
2)更换SM338模块和SM331模块。
3)根据现场CPU模块型号及版本情况,对PLC程序内硬件配置情况进行了修改完善,并重新下装到PLC。
4)将PLC程序存储卡格式化后重新写入新程序。
目前模块仍出现SF故障告警,请求指教

问题补充:
1、已经更换过CPU模块。2、338-342是模拟量输出模块地址,352-356是位置量SM338模块地址,368-376是模拟量输入地址。这些地址在程序内都使用。3、I/O模块连接器也更换过,并紧固过。

佳答案

你检查一下你实际编程使用的地址,如PIW352等输入地址是否与硬件组态范围内的地址编号。
回答补充问题:
既然这些使用的模拟量地址都在组态范围,那只能是你模块后“U”型连接器没有插到位,或者前连接器的24V电源丢失引起了。

若有收获,就点个赞吧!

文章来源于网络及文献如有侵权请联系站长
分享到:

微信扫一扫分享

阅读与本文标签相同的文章

相关推荐

最新文章 热门文章
最新课程 免费课程
PLC资料下载 电工电气资料下载
应用新秀
变频器故障代码查询APP
伺服故障代码查询APP
技成
手机APP
热门标签