CPU314频繁死机.

刘玉蓉 发布于2014-11-10 17:24 1 0 标签:

CPU314没有规律频繁停机需要手动才能运行,MMC卡、CPU、电源、U型连接器都换了,还是不行,程序里也没有空的输入输出点。接口模块用的IM365,也换了。有个CP343-1,没有换,不知道是不是这个原因。怀疑是有模块故障。请指点。

Event 2 of 10:  Event ID 16# 1381
Request for manual warm restart 
STOP due to: STOP caused by I/O management 
Startup information:
- Startup without modified system configuration 
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type: 
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on: 
- Warm restart triggered by switch setting; last power on backed up 
OB number: 100
Priority class: 27
Incoming event
03:28:32:307 pm  07/04/14


Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP 
STOP due to: STOP caused by I/O management 
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up 
Previous operating mode: STOP (internal) 
Requested operating mode: STARTUP (warm restart)
Incoming event
03:28:31:873 pm  07/04/14


Event 4 of 10:  Event ID 16# 5961
Parameter assignment error in CPU module parameters
Parameter: module type
Input address:   2004   of the module with parameter assignment errors
Error type: type ID not detected ID
Operating mode: STOP (internal)
External error, Incoming event
03:28:04:228 pm  07/04/14


Event 5 of 10:  Event ID 16# 5961
Parameter assignment error in CPU module parameters
Parameter: module type
Input address:   2000   of the module with parameter assignment errors
Error type: type ID not detected ID
Operating mode: STOP (internal)
External error, Incoming event
03:28:04:228 pm  07/04/14


Event 6 of 10:  Event ID 16# 4358
All modules are ready for operation 
Operating mode: STOP (internal)
Incoming event
03:28:04:131 pm  07/04/14

问题补充:
CP型号和组态不一致,但是CP也没有故障。是不规则的停机啊,如果组态不一致CPU就会报故障,为什么不规则停机。是不是和干扰有关系

佳答案

添加一些故障处理的空OB块,软启动块OB100。检查硬件是否分配了输入地址2000-2007。检查通讯是否正常。

若有收获,就点个赞吧!