S7-PLCSIM模拟器SF灯总是突然亮,帮我看看.

刘玉蓉 发布于2014-11-28 17:51 3 0 标签:

Event 1 of 80:  Event ID 16# 530D
New startup information in STOP mode
Startup prevented by:
- STOP request exists
- Cold restart or warm restart necessary
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Operating mode: STOP (internal)
Incoming event
10:33:54.778 AM  03/13/2014
(Coding: 16# 530D  FF04  C777  0041  0810  7710)


Event 2 of 80:  Event ID 16# 4568
STOP caused by time error (OB not loaded, or not possible, or no FRB) 
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
10:33:54.778 AM  03/13/2014
(Coding: 16# 4568  FF84  0000  0000  0000  0000)


Event 3 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.775 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 4 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.771 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 5 of 80:  Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB  37) 
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.735 AM  03/13/2014
(Coding: 16# 3502  FE50  C358  0000  1138  0E25)


Event 6 of 80:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:01:51.614 AM  03/13/2014
(Coding: 16# 4302  FF68  C700  0000  0810  7710)

佳答案

Causing OB: Cyclic interrupt OB (OB  37) 
循环中断错误

Requested OB: Timing error OB (OB80)
需要下载OB80块

原因:估计是你在OB37中的程序太多,运算时间超出了OB37的中断时间。
解决办法:
1、精简OB37中的程序
2、将OB37中的程序放到OB35中
3、下载OB80块,CPU会报错,但不会停机

若有收获,就点个赞吧!